This Domae product is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected poles and 6A In rated current and C tripping curve. The Icn rated short circuit breaking capacity is up to 6000A at 230VAC conforming to EN/IEC 60898-1 standard. This product complies with IEC 60898-1 standard. This miniature circuit breaker combines functions of circuit protection against short circuit and overload current, control and isolation. The fault tripping is indicated on the front panel by the position of the handle (O-I engraved). It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 230VAC. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 81mm x (D) 78.5mm. The weight is 0.095kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 70°C.
Main | |
Range | Domae |
Product or component type | Miniature circuit-breaker |
Device short name | Domae MCB |
Device application | Distribution |
Poles description | 1P |
Number of protected poles | 1 |
[In] rated current | 6 A |
Network type | AC |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | Icn 6000 A |
Complementary | |
Network frequency | 50/60 Hz |
[Ue] rated operational voltage | 230 V AC 50/60 Hz |
Magnetic tripping limit | 5...10 x In |
[Ics] rated service breaking capacity | 6000 kA 100 % x Icn conforming to EN/IEC 60898-1 |
Contact position indicator | Yes |
Control type | Toggle |
Local signalling | Fault trip |
Mounting mode | Clip-on |
Mounting support | DIN rail |
Comb busbar and distribution block compatibility | YES |
Connection pitch | 18 mm between devices |
9 mm pitches | 2 |
Height | 81 mm |
Width | 18 mm |
Depth | 78.5 mm |
Net weight | 0.095 kg |
Colour | White |
Mechanical durability | 20000 cycles |
Connections - terminals | Tunnel type terminals (top or bottom) - 1...25 mm² - rigid |
Wire stripping length | 14 mm for top or bottom connection |
Tightening torque | 2 N.m top or bottom |
Earth-leakage protection | Without |
Environment | |
Standards | IEC 60898-1 |
IP degree of protection | IP20 conforming to IEC 60529 |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
Ambient air temperature for operation | -25…60 °C |
Ambient air temperature for storage | -40…70 °C |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 7.3 cm |
Package 1 Width | 1.8 cm |
Package 1 Length | 8.5 cm |
Package 1 Weight | 98.0 g |
Unit Type of Package 2 | BB1 |
Number of Units in Package 2 | 12 |
Package 2 Height | 8.0 cm |
Package 2 Width | 8.8 cm |
Package 2 Length | 22.0 cm |
Package 2 Weight | 1.192 kg |
Unit Type of Package 3 | S03 |
Number of Units in Package 3 | 144 |
Package 3 Height | 30.0 cm |
Package 3 Width | 30.0 cm |
Package 3 Length | 40.0 cm |
Package 3 Weight | 14.918 kg |
Powered by Froala Editor