Send Us Your Whatsapp Number For Updates.
Code:
Number:

Need
Help?
Live Chat
+92309-9142797
PRODUCTS DETAILS
NEW | USED
ATV610D45N4Z

Product Description:

Description

This Easy Altivar 610 drive is a frequency inverter for three-phase asynchronous motors. It works at a rated supply voltage from 380V to 460V AC. It is suitable for motors with power rating up to 45kW / 60hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 37kW / 50hp for applications requiring significant overload (up to 150%). It offers a plug & play solution, whereby parameters are preset in the factory to the desired configuration, to help save process control and operating time. It has integrated radio interference input filters in accordance with the EMC standard category C3 in environment 1 or 2. It weighs 35.590kg and its dimensions are, 212mm wide, 600mm high, 262mm deep. this drive has been specially designed for standard applications in the market segments water and wastewater and oil and gas and in the domains process and machine management and building management.

Specifications

Main

Range of product

 

Easy Altivar 610

 

Product or component type

 

Variable speed drive

 

Product specific application

 

Fan, pump, compressor, conveyor

 

Device short name

 

ATV610

 

variant

 

Standard version

 

Product destination

 

Asynchronous motors

 

Mounting mode

 

Cabinet mount

 

EMC filter

 

Integrated conforming to EN/IEC 61800-3 category C3 with 50 m

 

IP degree of protection

 

IP20

 

Type of cooling

 

Forced convection

 

Supply frequency

 

50...60 Hz +/-5 %

 

Network number of phases

 

3 phases

 

[Us] rated supply voltage

 

380...460 V - 15...10 %

 

Motor power kW

 

45 kW for normal duty
 37 kW for heavy duty

 

Motor power hp

 

60 hp for normal duty
 50 hp for heavy duty

 

Line current

 

92.9 A at 380 V (normal duty)
 82.7 A at 460 V (normal duty)
 80.5 A at 380 V (heavy duty)
 69.6 A at 460 V (heavy duty)

 

Prospective line Isc

 

22 kA

 

Apparent power

 

65.9 kVA at 460 V (normal duty)
 55.4 kVA at 460 V (heavy duty)

 

Continuous output current

 

82.7 A at 4 kHz for normal duty
 69.6 A at 4 kHz for heavy duty

 

Maximum transient current

 

97 A during 60 s (normal duty)
 112 A during 60 s (heavy duty)

 

Asynchronous motor control profile

 

Optimized torque mode
 Constant torque standard
 Variable torque standard

 

Output frequency

 

0.0001…0.5 kHz

 

Nominal switching frequency

 

4 kHz

 

Switching frequency

 

2...12 kHz adjustable

 

number of preset speeds

 

16 preset speeds

 

Communication port protocol

 

Modbus serial

 

Option card

 

Slot A: communication card, Profibus DP V1
 Slot A: digital or analog I/O extension card
 Slot A: relay output card

 

 

Complementary

Output voltage

 

<= power supply voltage

 

Motor slip compensation

 

Automatic whatever the load
 Adjustable
 Not available in permanent magnet motor law
 Can be suppressed

 

Acceleration and deceleration ramps

 

Linear adjustable separately from 0.01 to 9000 s
 S, U or customized

 

Braking to standstill

 

By DC injection

 

Protection type

 

Thermal protection: motor
 Motor phase break: motor
 Thermal protection: drive
 Overheating: drive
 Overcurrent between output phases and earth: drive
 Overload of output voltage: drive
 Short-circuit protection: drive
 Motor phase break: drive
 Overvoltages on the DC bus: drive
 Line supply overvoltage: drive
 Line supply undervoltage: drive
 Line supply phase loss: drive
 Overspeed: drive
 Break on the control circuit: drive

 

Frequency resolution

 

Display unit: 0.1 Hz
 Analog input: 0.012/50 Hz

 

Electrical connection

 

Control, screw terminal: 0.5...1.5 mm²
 Line side, screw terminal: 35...50 mm²
 Motor, screw terminal: 50 mm²

 

Connector type

 

1 RJ45 (on lower part) for Modbus serial

 

Physical interface

 

2-wire RS 485 for Modbus serial

 

Transmission frame

 

RTU for Modbus serial

 

Transmission rate

 

4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial

 

Type of polarization

 

No impedance for Modbus serial

 

Number of addresses

 

1…247 for Modbus serial

 

Method of access

 

Slave

 

Supply

 

External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
 Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection

 

Local signalling

 

2 LEDs for local diagnostic
 1 LED (yellow) for embedded communication status
 2 LEDs (dual colour) for communication module status
 1 LED (red) for presence of voltage

 

Width

 

212.0 mm

 

Height

 

600.0 mm

 

Depth

 

262.0 mm

 

Net weight

 

25.295 kg

 

Analogue input number

 

3

 

Analogue input type

 

AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits
 AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
 AI2, AI3 software-configurable temperature probe or water level sensor

 

Discrete input number

 

6

 

Discrete input type

 

DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm
 DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)

 

Input compatibility

 

DI1...DI6: logic input level 1 PLC conforming to EN/IEC 61131-2
 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68

 

Discrete input logic

 

Positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)
 Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1)
 Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)

 

Analogue output number

 

2

 

Analogue output type

 

Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
 Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits

 

Sampling duration

 

5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
 2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input
 5 ms +/- 1 ms (DI5, DI6)configurable - pulse input
 10 ms +/- 1 ms (AQ1, AQ2) - analog output

 

Accuracy

 

+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
 +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output

 

Linearity error

 

AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
 AQ1, AQ2: +/- 0.2 % for analog output

 

Relay output number

 

3

 

Relay output type

 

Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
 Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
 Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles

 

Refresh time

 

Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)

 

Minimum switching current

 

Relay output R1, R2, R3: 5 mA at 24 V DC

 

Maximum switching current

 

Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
 Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
 Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
 Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC

 

Isolation

 

Between power and control terminals

 

Insulation resistance

 

> 1 MOhm 500 V DC for 1 minute to earth

 

 

Environment

Noise level

 

75 dB conforming to 86/188/EEC

 

Power dissipation in W

 

1000 W(forced convection) at 380 V, switching frequency 4 kHz
 121 W(natural convection) at 380 V, switching frequency 4 kHz

 

Volume of cooling air

 

240 m3/h

 

operating position

 

Vertical +/- 10 degree

 

Electromagnetic compatibility

 

Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6

 

Pollution degree

 

2 conforming to EN/IEC 61800-5-1

 

Vibration resistance

 

1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6

 

Shock resistance

 

15 gn for 11 ms conforming to IEC 60068-2-27

 

Relative humidity

 

5…95 % without condensation conforming to IEC 60068-2-3

 

Ambient air temperature for operation

 

-15…45 °C (without derating)
 45…60 °C (with derating factor)

 

Ambient air temperature for storage

 

-40…70 °C

 

Operating altitude

 

<= 1000 m without derating
 1000...4800 m with current derating 1 % per 100 m

 

Environmental characteristic

 

Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
 Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3

 

Standards

 

EN/IEC 61800-3
 Environment 2 category C3 EN/IEC 61800-3
 EN/IEC 61800-5-1
 IEC 60721-3

 

Marking

 

CE

 

 

Packing Units

Unit Type of Package 1

 

PCE

 

Number of Units in Package 1

 

1

 

Package 1 Height

 

26.5 cm

 

Package 1 Width

 

21.0 cm

 

Package 1 Length

 

60.0 cm

 

Package 1 Weight

 

35.59 kg

 

 

Powered by Froala Editor