This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 25m cable conforming to category C3. It works at a rated supply voltage from 500V to 690VAC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 75kW/100HP (500V supply voltage) for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 55kW/75HP (500V supply voltage) for applications requiring significant overload (up to 150%). Its dimensions are 331mm (width) x 297mm (depth) x 630mm (height). It weighs 53kg. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. This product is certified by CE, CSA and TUV. It meets UL 508C, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508 and IEC 13849-1 standards. Accessories (fan kit, graphic display terminal) and options (line chokes, dv/dt filter, sinus filter, EMC filter) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
Specifications
Main | |
Range of product | Altivar Process ATV600 |
Product or component type | Variable speed drive |
Product specific application | Process and utilities |
Device short name | ATV630 |
variant | Standard version |
Product destination | Asynchronous motors |
EMC filter | Integrated with 25 m conforming to EN/IEC 61800-3 category C3 |
IP degree of protection | IP00 conforming to IEC 61800-5-1 |
[Us] rated supply voltage | 500...690 V |
Type of cooling | Forced convection |
Supply frequency | 50...60 Hz - 5...5 % |
[Us] rated supply voltage | 500...690 V - 15...10 % |
Motor power kW | 55 kW at 500 V (normal duty) |
Motor power hp | 75 hp at 500 V normal duty |
Line current | 82.7 A at 500 V (normal duty) |
Prospective line Isc | 70 kA |
Apparent power | 104.8 kVA at 690 V (normal duty) |
Continuous output current | 83 A at 2.5 kHz for normal duty |
Maximum transient current | 91.3 A during 60 s (normal duty) |
Asynchronous motor control profile | Optimized torque mode |
Synchronous motor control profile | Permanent magnet motor |
Speed drive output frequency | 0.1…500 Hz |
Nominal switching frequency | 2.5 kHz |
Switching frequency | 1...4.9 kHz adjustable |
Safety function | STO (safe torque off) SIL 3 |
Discrete input logic | 16 preset speeds |
Communication port protocol | Ethernet |
Option card | Slot A: communication module, Profibus DP V1 |
Complementary | |
Mounting mode | Wall mount |
Network number of phases | 3 phases |
Discrete output number | 0 |
Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA |
Output voltage | <= power supply voltage |
Permissible temporary current boost | 1.1 x In during 60 s (normal duty) |
Motor slip compensation | Can be suppressed |
Acceleration and deceleration ramps | S, U or customized |
Physical interface | Ethernet |
Braking to standstill | By DC injection |
Protection type | Thermal protection: motor |
Transmission rate | 10, 100 Mbits |
Frequency resolution | Display unit: 0.1 Hz |
Transmission frame | RTU |
Electrical connection | Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 |
Connector type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP |
Data format | 8 bits, configurable odd, even or no parity |
type of polarization | No impedance |
Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
Number of addresses | 1…247 for Modbus serial |
Method of access | Slave Modbus TCP |
Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection |
Local signalling | 3 LEDs for local diagnostic |
Width | 331 mm |
Height | 630 mm |
Depth | 297 mm |
Net weight | 53 kg |
Analogue input number | 3 |
Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
Discrete input number | 8 |
Discrete input type | DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
Input compatibility | DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2 |
Discrete input logic | Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) |
Analogue output number | 2 |
Analogue output type | Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
Sampling duration | 2 ms +/- 0.5 ms (DI1...DI4) - discrete input |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input |
Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input |
Relay output number | 3 |
Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles |
Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC |
Isolation | Between power and control terminals |
Maximum output frequency | 500 kHz |
Maximum input current | 87.7 A |
Quantity per set | 1 |
Enclosure mounting | Wall mounted |
Environment | |
Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Noise level | 52 dB conforming to 86/188/EEC |
Power dissipation in W | Natural convection: 268 W at 500 V, switching frequency 2.5 kHz |
Volume of cooling air | 406 m3/h |
operating position | Vertical +/- 10 degree |
Maximum THDI | <48 % with external line choke conforming to IEC 61000-3-12 |
Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 |
Pollution degree | 2 conforming to EN/IEC 61800-5-1 |
Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
Ambient air temperature for operation | -15…50 °C (without derating) |
Ambient air temperature for storage | -40…70 °C |
Operating altitude | <= 1000 m without derating |
Standards | UL 508C |
Product certifications | TÜV |
Marking | CE |
Standards | UL 508C |
Overvoltage category | III |
Regulation loop | Adjustable PID regulator |
noise level | 56 dB |
Pollution degree | 2 |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 61.0 cm |
Package 1 Width | 50.0 cm |
Package 1 Length | 120.0 cm |
Package 1 Weight | 50.5 kg |
Powered by Froala Editor