This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 200V to 240V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 5.5kW / 7.5hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 4kW / 5hp for applications requiring significant overload (up to 150%). It weighs 7.7kg and its dimensions are, 171mm wide, 409mm high, 233mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.

Specifications

Main

Range of product

 

Altivar Process ATV600

 

Product or component type

 

Variable speed drive

 

Product specific application

 

Process and utilities

 

Device short name

 

ATV630

 

variant

 

Standard version

 

Product destination

 

Asynchronous motors
 Synchronous motors

 

EMC filter

 

Without EMC filter

 

IP degree of protection

 

IP21 conforming to IEC 61800-5-1
 IP21 conforming to IEC 60529

 

[Us] rated supply voltage

 

200...240 V

 

Degree of protection

 

UL type 1 conforming to UL 508C

 

Type of cooling

 

Forced convection

 

Supply frequency

 

50...60 Hz - 5...5 %

 

[Us] rated supply voltage

 

200...240 V - 15...10 %

 

Motor power kW

 

5.5 kW (normal duty)
 4 kW (heavy duty)

 

Motor power hp

 

7.5 hp normal duty
 5 hp heavy duty

 

Line current

 

20.2 A at 200 V (normal duty)
 17.1 A at 240 V (normal duty)
 15.1 A at 200 V (heavy duty)
 13 A at 240 V (heavy duty)

 

Prospective line Isc

 

50 kA

 

Apparent power

 

7.1 kVA at 240 V (normal duty)
 5.4 kVA at 240 V (heavy duty)

 

Continuous output current

 

25.4 A at 4 kHz for normal duty
 18.7 A at 4 kHz for heavy duty

 

Maximum transient current

 

27.9 A during 60 s (normal duty)
 28.1 A during 60 s (heavy duty)

 

Asynchronous motor control profile

 

Optimized torque mode
 Constant torque standard
 Variable torque standard

 

Synchronous motor control profile

 

Permanent magnet motor
 Synchronous reluctance motor

 

Speed drive output frequency

 

0.1…500 Hz

 

Nominal switching frequency

 

4 kHz

 

Switching frequency

 

2...12 kHz adjustable
 4...12 kHz with derating factor

 

Safety function

 

STO (safe torque off) SIL 3

 

Discrete input logic

 

16 preset speeds

 

Communication port protocol

 

Modbus serial
 Modbus TCP
 Ethernet

 

Option card

 

Slot A: communication module, Profibus DP V1
 Slot A: communication module, PROFINET
 Slot A: communication module, DeviceNet
 Slot A: communication module, Modbus TCP/EtherNet/IP
 Slot A: communication module, CANopen daisy chain RJ45
 Slot A: communication module, CANopen SUB-D 9
 Slot A: communication module, CANopen screw terminals
 Slot A/slot B: digital and analog I/O extension module
 Slot A/slot B: output relay extension module
 Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
 Communication module, BACnet MS/TP
 Communication module, Ethernet Powerlink

 

 

Complementary

Mounting mode

 

Wall mount

 

Network number of phases

 

3 phases

 

Discrete output number

 

0

 

Discrete output type

 

Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
 Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
 Relay outputs R2A, R2C 250 V AC 5000 mA
 Relay outputs R2A, R2C 30 V DC 5000 mA
 Relay outputs R3A, R3C 250 V AC 5000 mA
 Relay outputs R3A, R3C 30 V DC 5000 mA

 

Output voltage

 

<= power supply voltage

 

Permissible temporary current boost

 

1.1 x In during 60 s (normal duty)
 1.5 x In during 60 s (heavy duty)

 

Motor slip compensation

 

Can be suppressed
 Not available in permanent magnet motor law
 Adjustable
 Automatic whatever the load

 

Acceleration and deceleration ramps

 

Linear adjustable separately from 0.01...9999 s

 

Physical interface

 

Ethernet
 2-wire RS 485

 

Braking to standstill

 

By DC injection

 

Protection type

 

Thermal protection: motor
 Safe torque off: motor
 Motor phase break: motor
 Thermal protection: drive
 Safe torque off: drive
 Overheating: drive
 Overcurrent between output phases and earth: drive
 Overload of output voltage: drive
 Short-circuit protection: drive
 Motor phase break: drive
 Overvoltages on the DC bus: drive
 Line supply overvoltage: drive
 Line supply undervoltage: drive
 Line supply phase loss: drive
 Overspeed: drive
 Break on the control circuit: drive

 

Transmission rate

 

10, 100 Mbits
 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps

 

Frequency resolution

 

Display unit: 0.1 Hz
 Analog input: 0.012/50 Hz

 

Transmission frame

 

RTU

 

Electrical connection

 

Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16
 Motor: screw terminal 10 mm²/AWG 8
 Line side: screw terminal 6 mm²/AWG 10

 

Connector type

 

RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
 RJ45 (on the remote graphic terminal) for Modbus serial

 

Data format

 

8 bits, configurable odd, even or no parity

 

type of polarization

 

No impedance

 

Exchange mode

 

Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP

 

Number of addresses

 

1…247 for Modbus serial

 

Method of access

 

Slave Modbus TCP

 

Supply

 

External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
 Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
 Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection

 

Local signalling

 

3 LEDs for local diagnostic
 3 LEDs (dual colour) for embedded communication status
 4 LEDs (dual colour) for communication module status
 1 LED (red) for presence of voltage

 

Width

 

171 mm

 

Height

 

409 mm

 

Depth

 

233 mm

 

Net weight

 

7.7 kg

 

Analogue input number

 

3

 

Analogue input type

 

AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
 AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
 AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits

 

Discrete input number

 

8

 

Discrete input type

 

DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)

 

Input compatibility

 

DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
 DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2

 

Discrete input logic

 

Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)
 Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)

 

Analogue output number

 

2

 

Analogue output type

 

Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
 Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
 Software-configurable current DQ-, DQ+: 30 V DC
 Software-configurable current DQ-, DQ+: 100 mA

 

Sampling duration

 

2 ms +/- 0.5 ms (DI1...DI4) - discrete input
 5 ms +/- 1 ms (DI5, DI6) - discrete input
 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
 10 ms +/- 1 ms (AO1) - analog output

 

Accuracy

 

+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
 +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output

 

Linearity error

 

AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
 AO1, AO2: +/- 0.2 % for analog output

 

Relay output number

 

3

 

Relay output type

 

Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
 Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
 Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles

 

Refresh time

 

Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)

 

Minimum switching current

 

Relay output R1, R2, R3: 5 mA at 24 V DC

 

Maximum switching current

 

Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
 Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
 Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
 Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC

 

Isolation

 

Between power and control terminals

 

Maximum output frequency

 

500 kHz

 

Maximum input current

 

20.2 A

 

Variable speed drive application selection

 

Building - HVAC compressor centrifugal
 Food and beverage processing other application
 Mining mineral and metal fan
 Mining mineral and metal pump
 Oil and gas fan
 Water and waste water other application
 Building - HVAC screw compressor
 Food and beverage processing pump
 Food and beverage processing fan
 Food and beverage processing atomization
 Oil and gas electro submersible pump (ESP)
 Oil and gas water injection pump
 Oil and gas jet fuel pump
 Oil and gas compressor for refinery
 Water and waste water centrifuge pump
 Water and waste water positive displacement pump
 Water and waste water electro submersible pump (ESP)
 Water and waste water screw pump
 Water and waste water lobe compressor
 Water and waste water screw compressor
 Water and waste water compressor centrifugal
 Water and waste water fan
 Water and waste water conveyor
 Water and waste water mixer

 

Motor power range AC-3

 

4…6 kW at 200…240 V 3 phases

 

Quantity per set

 

1

 

Enclosure mounting

 

Wall mounted

 

 

Environment

Insulation resistance

 

> 1 MOhm 500 V DC for 1 minute to earth

 

Noise level

 

56 dB conforming to 86/188/EEC

 

Power dissipation in W

 

Natural convection: 47 W at 200 V, switching frequency 4 kHz
 Forced convection: 179 W at 200 V, switching frequency 4 kHz

 

Volume of cooling air

 

103 m3/h

 

operating position

 

Vertical +/- 10 degree

 

Maximum THDI

 

<48 % from 80...100 % of load conforming to IEC 61000-3-12

 

Electromagnetic compatibility

 

Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6

 

Pollution degree

 

2 conforming to EN/IEC 61800-5-1

 

Vibration resistance

 

1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6

 

Shock resistance

 

15 gn for 11 ms conforming to IEC 60068-2-27

 

Relative humidity

 

5…95 % without condensation conforming to IEC 60068-2-3

 

Ambient air temperature for operation

 

-15…50 °C (without derating)
 50…60 °C (with derating factor)

 

Ambient air temperature for storage

 

-40…70 °C

 

Operating altitude

 

<= 1000 m without derating
 1000...4800 m with current derating 1 % per 100 m

 

Standards

 

UL 508C
 EN/IEC 61800-3
 Environment 1 category C2 EN/IEC 61800-3
 Environment 2 category C3 EN/IEC 61800-3
 EN/IEC 61800-5-1
 IEC 61000-3-12
 IEC 60721-3
 IEC 61508
 IEC 13849-1

 

Product certifications

 

UL
 ATEX zone 2/22
 CSA
 DNV-GL
 TÜV
 ATEX INERIS

 

Marking

 

CE

 

Standards

 

UL 508C
 EN/IEC 61800-3
 EN/IEC 61800-3 environment 1 category C2
 EN/IEC 61800-3 environment 2 category C3
 EN/IEC 61800-5-1
 IEC 61000-3-12
 IEC 60721-3
 IEC 61508
 IEC 13849-1

 

Overvoltage category

 

III

 

Regulation loop

 

Adjustable PID regulator

 

noise level

 

56 dB

 

Pollution degree

 

2

 

 

Packing Units

Unit Type of Package 1

 

PCE

 

Number of Units in Package 1

 

1

 

Package 1 Height

 

21.500 cm

 

Package 1 Width

 

58.000 cm

 

Package 1 Length

 

35.000 cm

 

Package 1 Weight

 

10.203 kg

 

Unit Type of Package 2

 

P06

 

Number of Units in Package 2

 

3

 

Package 2 Height

 

75.000 cm

 

Package 2 Width

 

60.000 cm

 

Package 2 Length

 

80.000 cm

 

Package 2 Weight

 

43.609 kg

 

 

Powered by Froala Editor