METSEPM2130

Product Description:

Description

This device is a panel mount or flush mount power meter with a 96mm by 96mm bezel size having 3 rows of bright red 4 digits 14.2 mm height LED display. The meter measures active energy as per accuracy class Class 0.5S complying to IEC 62053-22 standard with sampling rate of 64 samples per cycle. Able to measures all three vectors of power and energy such as Active, Apparent & Reactive beside Voltages, Current, Frequency and Power Factor. Plus the total Harmonic Distortion and Individual harmonics up to 31st Harmonic order. The meter will function in either 50Hz or 60Hz network frequency and accepts universal control power voltages ranging from 80 to 300 V Line to Neutral AC or DC voltages. Rated current for this meter is either 1A or 5A input. it supports up to 13 different types of wiring schemes under Single Phase, Two Phase or Three Phase configuration types. The range of measurement voltage between Phases is 35 to 480 V Line to Line AC at 45 to 65 Hz while it is 20 to 277 V between Line and Neutral. It is having RS485 communication port over Modbus RTU protocol. The meter can be upgraded with optional add on IO modules for WAGES monitoring. These module comes with either two channels each of digital inputs and outputs or analog inputs and outputs. This version can be configured for 23 different types of alarms stored in 40 registers. Product dimensions are as follows: width 3.78 in (96 mm), depth 2.16 in (54 mm), height 3.78 in (96 mm) and product weight 10.58 oz (300 g).

Specifications

Main

Range

EasyLogic

Product name

EasyLogic PM2100

Device short name

PM2130

Product or component type

Power meter

 

Complementary

Device application

Sub billing
 Power monitoring

Power quality analysis

Total harmonic distortion
 up to the 31st harmonic

Type of measurement

Apparent power min/max, total
 Active and reactive power min/max, total
 Current min/max, avg
 Voltage min/max, avg
 Frequency min/max, avg
 Total current harmonic distortion THD (I) per phase
 Total voltage harmonic distortion THD (U) per phase
 Power factor min/max, avg
 Apparent energy total
 Active and reactive energy total

Metering type

Peak demand currents
 Active power P, P1, P2, P3
 Demand power P, Q, S
 Reactive power Q, Q1, Q2, Q3
 Apparent power S, S1, S2, S3
 Active, reactive, apparent energy (signed, four quadrant)
 Voltage U, U21, U32, U13, V, V1, V2, V3
 Current I, I1, I2, I3
 Calculated neutral current
 Unbalance current
 Peak demand power PM, QM, SM

Accuracy class

Class 1 reactive energy conforming to IEC 62053-24
 Class 0.5S active energy conforming to IEC 62053-22
 Class 5 harmonic distorsion (I THD & U THD)

Measurement accuracy

Apparent power +/- 0.5 %
 Active energy +/- 0.5 %
 Reactive energy +/- 1 %
 Active power +/- 0.5 %
 Voltage +/- 0.5 %
 Power factor +/- 0.01
 Current +/- 0.5 %
 Frequency +/- 0.05 %

Measurement current

5…6000 mA

Measurement voltage

35…480 V AC 50/60 Hz between phases
 20…277 V AC 50/60 Hz between phase and neutral
 480…999000 V AC 50/60 Hz with external VT

Frequency measurement range

45…65 Hz

[Us] rated supply voltage

80...277 V AC 45...65 Hz +/- 10 %
 100...277 V DC +/- 10 %

Network frequency

50 Hz
 60 Hz

Ride-through time

50 ms 120 V AC typical
 50 ms 230 V AC typical
 50 ms 125 V DC typical

[In] rated current

1 A
 5 A

Maximum power consumption in VA

8 VA at 277 V AC

Maximum power consumption in W

3.3 W (power lines (AC))
 3.3 W at 277 V (power lines (DC))

input impedance

Current (impedance <= 0.3 mOhm)
 Voltage (impedance > 5 MOhm)

Tamperproof of settings

Protected by access code

Display type

7 segments LED

Display colour

Red

messages display capacity

3 fields of 4 characters

Display digits

12 digit(s) - 14.2 mm in height

Demand intervals

Configurable from 1 to 60 min

Information displayed

Demand current (past value)
 Demand current (present value)
 Demand power (past value)
 Demand power (present value)
 Voltage
 Current
 Frequency
 Energy consumption
 Harmonic distortion
 Power factor
 Active power
 Apparent power
 Reactive power
 Unbalanced in %

Control type

3 x button

Local signalling

Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
 Green LED: module operation and integrated communication

Number of inputs

0

Number of outputs

0

Communication port protocol

Modbus RTU at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V

Communication port support

Screw terminal block: RS485

Data recording

Power logs
 Time stamping
 Energy consumption logs
 Min/max for 8 parameters

Function available

Real time clock

Sampling rate

64 samples/cycle

Cybersecurity

Enable/disable communication ports

Communication service

Remote monitoring

Product certifications

CE conforming to IEC 61010-1
 CULus conforming to UL 61010-1
 CULus conforming to CSA C22.2 No 61010-1
 RCM
 EAC
 C-Tick

Mounting mode

Clip-on

Mounting position

Vertical

Mounting support

Framework

Provided equipment

1 x installation guide

Measurement category

Category III 480 V
 Category II 480…600 V

Electrical insulation class

Class II
 Double insulation

Flame retardance

V-0 conforming to UL 94

Connections - terminals

Current transformer: screw connection (bottom) 6
 Voltage inputs: screw connection (top) 4

Material

Polycarbonate

Width

96 mm

Depth

76.09 mm total:
 61.64 mm embedded:

Height

96 mm

Net weight

300 g

Compatibility code

PM2130

 

Environment

Service life

7 year(s)

IP degree of protection

IP54 front: conforming to IEC 60529
 IP30 body: conforming to IEC 60529

Relative humidity

5…95 % at 50 °C

Pollution degree

2

Ambient air temperature for operation

-10…60 °C

Ambient air temperature for storage

-25…70 °C

Operating altitude

<= 2000 m

Electromagnetic compatibility

Electrostatic discharge conforming to IEC 61000-4-2
 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
 Surge immunity test conforming to IEC 61000-4-5
 Conducted RF disturbances conforming to IEC 61000-4-6
 Magnetic field at power frequency conforming to IEC 61000-4-8
 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
 Emission tests conforming to FCC part 15 class A

Overvoltage category

III

 

Packing Units

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

11.5 cm

Package 1 Width

8.7 cm

Package 1 Length

12.0 cm

Package 1 Weight

404.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

18

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

7.71 kg

Unit Type of Package 3

P12

Number of Units in Package 3

432

Package 3 Height

80.0 cm

Package 3 Width

80.0 cm

Package 3 Length

120.0 cm

Package 3 Weight

197.112 kg

 

Powered by Froala Editor